Thermostat DIXELL XR06CX-5N0C0 Negative

DIXELLSKU: XR06CX-5N0C0

Marque DIXELL
État du Produit Neuf

Prix:
Prix réduit519.00 dh
Stock:
En stock

Description

Fiche technique

Producer DIXELL
Type XR06CX-5N0C0
Power absorption: 3.5VA max
Display: 2 digits, red LED, 14,2 mm high; Inputs: Up to 2 NTC
Digital Input: free voltage contact
Relay outputs (compressor): SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac or 20(8)A 250Vac
Defrost or Aux: SPDT 8(3) A, 250Vac
Data storing:  on the non-volatile memory (EEPROM)
Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C
Storage temperature: -25÷60 °C.
Relative humidity: 20÷85% (no condensing)
Resolution:  0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,1 °C ±1 digit; Accuracy (ambient temp. 25°C): ±0,1 °C ±1 digit

Description

DIXELL XR06CX controller – refrigeration controller with defrosting and fan control

The Dixell XR06CX is an advanced microprocessor-based temperature controller designed for use in low- and medium-temperature refrigeration systems. Its integrated defrosting and fan management functions make it a comprehensive solution for cold rooms, freezers, display cases, and refrigerated counters.

The controller supports two NTC sensors – for measuring room temperature and evaporator temperature – enabling precise control of both the compressor and the defrosting process, as well as fan operation.


Key features:

Compressor control using setpoint and temperature differential.

Support for two NTC sensors – room temperature and evaporator temperature (both included).

Automatic defrosting: with an electric heater or hot gas.

Advanced fan management with the option of continuous, cyclic, or delayed operation after defrosting.

Programmable digital input – e.g. for external alarm, door sensor, operating mode reversal.

Temperature and sensor error alarms with programmable delay.

Configuration via keyboard or HOT KEY tool – quick copying of settings.


Application:

Cold stores and freezers

Refrigerated display cases

Refrigerated cabinets and counters

Refrigeration equipment with hot gas or heater defrosting


Technical data:

Power supply: 230V AC ±10%, 50/60Hz

Equipment: 2 NTC sensors – length 1.5 m

Relay outputs:

  • Compressor: SPST 20(8)A 250V AC
  • Defrosting: SPDT 8(3)A 250V AC

Fan: SPST 8(3)A or 5(2)A 250V AC (depending on model)

Temperature measurement range: -40°C to +110°C

Resolution: 0.1°C or 1°C (adjustable)

Measurement accuracy: ±0.1°C at 25°C

Defrost type: electric heater or hot gas

Drip after defrost: programmable time (0–99 minutes)

Defrost end temperature: programmable in the range of -55°C to +50°C

Fan operating modes:

Dependent on compressor operation

Continuous with interruption during defrosting

Continuous also during defrosting

With delayed start after defrosting

Alarms: Sensor error (P1, P2), maximum and minimum temperature alarm, open door alarm

Dimensions (front): 32 x 74 mm

Installation depth: 60 mm

Installation: panel, 71 x 29 mm hole

Protection rating: IP65 (front panel), IP20 (housing)

Operating temperature: 0°C to +60°C

Relative humidity: 20–85% (non-condensing)

Settings memory: EEPROM


Why choose the XR06CX?

✅ Comprehensive control of cooling, defrosting, and fans

✅ Support for two sensors – greater precision and safety

✅ High reliability – a Dixell (Emerson Copeland) product

✅ Programmable alarms and digital input

✅ Easy HOT KEY programming – ideal for service


Order the DIXELL XR06CX controller and gain full control over temperature and defrosting!

Livraison et Retours

Documents

Produits Similaires

Vu Récemment