Description
Fiche technique
| Producer | DIXELL |
| Type | XR06CX-5N0C0 |
| Power absorption: | 3.5VA max |
| Display: | 2 digits, red LED, 14,2 mm high; Inputs: Up to 2 NTC |
| Digital Input: | free voltage contact |
| Relay outputs (compressor): | SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac or 20(8)A 250Vac |
| Defrost or Aux: | SPDT 8(3) A, 250Vac |
| Data storing: | on the non-volatile memory (EEPROM) |
| Rated impulsive voltage: | 2500V; Overvoltage Category: II |
| Operating temperature: | 0÷60 °C |
| Storage temperature: | -25÷60 °C. |
| Relative humidity: | 20÷85% (no condensing) |
| Resolution: | 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,1 °C ±1 digit; Accuracy (ambient temp. 25°C): ±0,1 °C ±1 digit |
Description
DIXELL XR06CX controller – refrigeration controller with defrosting and fan control
The Dixell XR06CX is an advanced microprocessor-based temperature controller designed for use in low- and medium-temperature refrigeration systems. Its integrated defrosting and fan management functions make it a comprehensive solution for cold rooms, freezers, display cases, and refrigerated counters.
The controller supports two NTC sensors – for measuring room temperature and evaporator temperature – enabling precise control of both the compressor and the defrosting process, as well as fan operation.
Key features:
Compressor control using setpoint and temperature differential.
Support for two NTC sensors – room temperature and evaporator temperature (both included).
Automatic defrosting: with an electric heater or hot gas.
Advanced fan management with the option of continuous, cyclic, or delayed operation after defrosting.
Programmable digital input – e.g. for external alarm, door sensor, operating mode reversal.
Temperature and sensor error alarms with programmable delay.
Configuration via keyboard or HOT KEY tool – quick copying of settings.
Application:
Cold stores and freezers
Refrigerated display cases
Refrigerated cabinets and counters
Refrigeration equipment with hot gas or heater defrosting
Technical data:
Power supply: 230V AC ±10%, 50/60Hz
Equipment: 2 NTC sensors – length 1.5 m
Relay outputs:
- Compressor: SPST 20(8)A 250V AC
- Defrosting: SPDT 8(3)A 250V AC
Fan: SPST 8(3)A or 5(2)A 250V AC (depending on model)
Temperature measurement range: -40°C to +110°C
Resolution: 0.1°C or 1°C (adjustable)
Measurement accuracy: ±0.1°C at 25°C
Defrost type: electric heater or hot gas
Drip after defrost: programmable time (0–99 minutes)
Defrost end temperature: programmable in the range of -55°C to +50°C
Fan operating modes:
Dependent on compressor operation
Continuous with interruption during defrosting
Continuous also during defrosting
With delayed start after defrosting
Alarms: Sensor error (P1, P2), maximum and minimum temperature alarm, open door alarm
Dimensions (front): 32 x 74 mm
Installation depth: 60 mm
Installation: panel, 71 x 29 mm hole
Protection rating: IP65 (front panel), IP20 (housing)
Operating temperature: 0°C to +60°C
Relative humidity: 20–85% (non-condensing)
Settings memory: EEPROM
Why choose the XR06CX?
✅ Comprehensive control of cooling, defrosting, and fans
✅ Support for two sensors – greater precision and safety
✅ High reliability – a Dixell (Emerson Copeland) product
✅ Programmable alarms and digital input
✅ Easy HOT KEY programming – ideal for service
Order the DIXELL XR06CX controller and gain full control over temperature and defrosting!